Identifying Temperature Sensor Type

TL;DR – Quick Summary

TL;DR – Quick Summary

To identify an unknown temperature sensor, check:

  1. Any markings or model info on the instrument.
  2. The temperature range it usually measures.
  3. The number and colour of wires (to match wiring standards).
  4. Its electrical resistance using a multimeter.

Most industrial temperature sensors are either:

Introduction

We often receive calls from customers holding a temperature sensor with no documentation and only a vague idea of what it might be. Sometimes, they’ll even say they have a “Pt100 thermocouple”—a term that mixes two completely different sensor technologies.

This guide will help you correctly identify the type of temperature sensor you have, using straightforward checks that anyone from a plant technician to a maintenance engineer can follow.

Main Temperature Sensor Categories

Most industrial contact temperature sensors fall into one of three categories:

  • Thermocouples – generate a voltage from dissimilar metals.
  • Resistance Thermometers (RTDs) – change resistance with temperature.
  • Thermistors – semiconductor devices with resistance highly dependent on temperature.

How to Identify a Temperature Sensor – Step-by-Step

Step 1: Instrumentation Information

This may not be straightforward due to Jargon. Possibilities are:

There is also a range of other less common sensor assemblies which exact but are extremely rare.

Step 2: Temperature Sensor Range

The temperature sensor range that each sensor type can work at can hold vital information as to which sensor the customer is currently using. The usual maximum temperatures of sensors can be summarised as below, however it is not an absolute limit and individual designs can have other limitations.

MI type k thermocouple with a head
Sensor Type Common limit
K 1100°C
J 800°C
N 1200°C
R 1500°C
S 1500°C
B 1600°C
RTD 500°C

Step 3: Quantity and Colour of Wires

Wire count and colour coding can be a giveaway:

  • 2 wires – Could be any type (thermocouple, RTD, thermistor).
  • 3 wires – Often a 3-wire RTD (two same-colour wires, one different).
  • 4 wires – Likely a 4-wire RTD (two wires of each colour).
  • Thermocouple colours – Follow IEC or ANSI standards; red is often negative in IEC, positive in ANSI.

Step 4: Physical Readings

Use a multimeter to measure resistance at room temperature:

  • < 10 Ω → Probably a thermocouple.
  • ~110 Ω → Pt100 RTD.
  • ~1100 Ω → Pt1000 RTD.
  • Higher resistance (e.g., kΩ range) → Likely a thermistor.

Open circuit → Sensor is faulty.

Common Misunderstanding: Pt100 Thermocouple

There is no such thing—a Pt100 is an RTD, not a thermocouple. Mixing the terms causes confusion and can lead to incorrect sensor replacement.

FAQ – Frequently Asked Questions

Q1: Can a thermistor be confused with an RTD?

Yes. Both have resistance that changes with temperature, but thermistors have much higher resistance and are more non-linear.

Q2: What if my sensor has no colour coding?

You’ll need to rely on resistance measurements and known temperature ranges to identify it.

Q3: Can thermocouples work at low temperatures?

Yes, but they are usually chosen for high-temperature applications where RTDs would be unsuitable.

Q4: Why measure resistance instead of voltage?

Resistance testing is safer and works when the sensor is disconnected from its circuit.

View our temperature sensors